NodeLoop

AWG ↔ mm² • Ampacity & Voltage Drop

Convert AWG to mm and mm², check ampacity (with bundling derating), compute voltage drop with temperature/material, and compare gauges visually. Includes exportable reference table.

Interconnected Tabs Voltage Drop Ampacity + Bundling Visualization CSV/JSON Export
Erratum
Updated
  • The FAQ said that selecting aluminum adjusts the ampacity, and that ambient temperature changes the suggested ampacity. Neither was implemented: the ampacity always comes from the copper chassis column, multiplied only by the bundling or custom derating factor. The FAQ now describes what the tool actually computes.
  • The "Power Transmission" column was described as a conduit / bundled-cable rating. It is the conservative 700 circular-mils-per-ampere rule from the PowerStream table that the data comes from.

Sources: PowerStream, "Wire Gauge and Current Limits" (source table).

Quick Actions

Gauge: — Ø — mm • — mm² Bundling: — • Derate: —% Material: Cu @ 20°C • ρ(T): —

All tabs share the same state — change values anywhere and it propagates.

Results

Diameter: mm

Area: mm²

Resistance: Ω/km

Ampacity (Chassis): A

Ampacity (Power Transmission): A

Adjusted Ampacity (bundling/custom): —

Rough NEC-style derating

Overrides automatic rule if set

These settings affect safety (ampacity). Voltage Drop uses material & temperature separately. Derating used: —%

Closest AWG Match: ---

AWG Diameter (mm) Area (mm²) Resistance (Ω/km) Ampacity (Chassis) Ampacity (Power)

Notes & References

Formulas

dₙ = 0.127 · 92^((36−n)/39) (mm)

Aₙ = (π/4) · dₙ² (mm²)

Standards

  • ASTM B258 — wire dimensions
  • NFPA 70 (NEC) — ampacity tables for installations (not the source of the chassis / power-transmission columns)
  • PowerStream wire gauge table — source of the chassis and power-transmission columns

Important

  • Voltage drop uses material & temperature — bundling affects ampacity (safety), not Vdrop directly.
  • Long runs: Vdrop can dominate over ampacity.
  • PCB traces need a different calculator.

Understanding AWG, Ampacity & Voltage Drop

American Wire Gauge (AWG) is a standardized system (mostly US) for round conductors. The higher the AWG number, the thinner the wire. Historically this follows the number of drawing steps required to reach the final size.

AWG → Diameter / Cross-Section (mm & mm²)

For gauge n:

  • Diameter (mm): dₙ = 0.127 × 92^((36 − n)/39)
  • Area (mm²): Aₙ = (π/4) × dₙ²

Note: the table used in this tool reflects common reference values (Cu ≈ 20 °C) to avoid runtime rounding drift.

Ampacity — Chassis vs Power Transmission

Ampacity is the continuous current a conductor can carry without exceeding its temperature rating (conductor + insulation + environment). Thermal dissipation is key:

  • Chassis wiring — short runs, open air, spaced wires ⇒ better convection ⇒ higher allowable current.
  • Power transmission — a very conservative rule of thumb of about 700 circular mils per ampere (for example 22 AWG ≈ 642 cmil ⇒ 0.92 A). It is not a conduit or bundling table.

Both columns come from the widely reproduced PowerStream wire table for copper. They are rules of thumb, not code values. For real installations, apply your local code tables and correction factors (e.g., NEC), which depend on insulation rating, ambient temperature and installation method.

Bundling / Derating

When multiple current-carrying conductors are bundled (harness, loom, conduit), heat removal is poorer. Apply a derating factor to nominal ampacity. In the tool, Bundled Conductors and Custom Derating adjust the safety ampacity (shown as an indicator in the Voltage Drop tab).

Why doesn’t derating change voltage drop?

Voltage drop is pure Ohm’s law: Vdrop = I × R. For a given area and material, R depends on resistivity (and thus temperature/material), not on whether a code allows you to run more or less current. Derating is a thermal/safety constraint, not a change to Ohm’s law. That’s why the tool shows derating as an ampacity diagnostic alongside (but separate from) the drop calculation.

Voltage Drop

For length L, Vdrop = I × R_total with R_total = R_line × L (one-way) or 2 × R_line × L (round-trip). The linear resistance R_line varies with material resistivity ρ and temperature:

  • Temperature dependence: ρ(T) = ρ₍20 °C₎ × [1 + α × (T − 20)]
  • The Ω/km table is for Cu ≈ 20 °C. The tool rescales it by the ratio ρ(T) / ρ_Cu@20 °C and respects the chosen material (Cu/Al/Custom).

At DC/50–60 Hz, skin effect is negligible for these sizes and can be ignored.

Materials, Stranding, Insulation

  • Copper vs Aluminum — Al has higher resistivity (~1.6× Cu), so for the same drop you need a larger area.
  • Solid vs stranded — bulk resistivity is essentially the same; stranded is about flexibility and terminations.
  • Insulation & temperature class (60/75/90 °C…) — limits ampacity, not Ohm’s law.

Practical selection workflow

  1. Check ampacity (apply bundling derate if needed).
  2. Check acceptable voltage drop at the load (e.g., <3 % for low-voltage DC lines).
  3. Pick the AWG that satisfies both.

Disclaimer

This tool provides reference values. For real installations, comply with applicable codes/standards (NEC, etc.), consider insulation rating, ambient temperatures, number of current-carrying conductors in the same pathway, and environmental conditions.

Frequently Asked Questions

Quick answers that highlight how to get the most from the converter, voltage-drop planner, and ampacity tools.

How do I pick the right AWG size with this tool?
Go to the Voltage Drop tab, enter your system voltage, run length, current, and maximum drop, then press Suggest Minimum AWG. The tool simulates every gauge and returns the smallest wire that keeps the drop within your target.
Does the converter support aluminum conductors?
For voltage drop, yes: select Aluminum in the Material dropdown on the Voltage Drop tab and the calculator uses aluminum resistivity and temperature coefficient. The ampacity values are not adjusted: they come from a copper reference table, so they do not apply to aluminum conductors.
How do I factor in bundled wires or ambient heat?
Set the number of bundled conductors, or enter your own derating percentage; the adjusted ampacity is the copper chassis-wiring value multiplied by that factor. Ambient temperature is not part of the ampacity calculation: it only changes the conductor resistance used for voltage drop. For an installation, use the ampacity tables and correction factors of your electrical code.
Can I export the reference table for offline work?
Yes. In the Reference Table section use Export CSV or Export JSON to download the full AWG data set, including diameter, area, resistance, and power or chassis ampacity columns.

Related tools

Built for makers and electricians.